KYN28A-12 Withdrawable Armored AC Metal-enclosed Switchgear

KYN28A-12 Withdrawable Armored AC Metal-enclosed Switchgear

Tags: High-voltage , Switchgear , Xinda

Email: xdhdbyq@gmail.com

Mobile: +8613053855050

Phone: 8618063599126

QQ: 3175898298

Product Details

KYN28A-12 Withdrawable Armored AC Metal-enclosed Switchgear
KYN28A-12 Withdrawable Armored AC Metal-enclosed Switchgear

I. Product Description

The KYN28A-12 Metal-clad Withdrawable AC Metal-enclosed Switchgear (hereinafter referred to as the Switchgear) is a new product independently designed and developed by our company based on the absorption of advanced manufacturing technologies from both domestic and international sources. It can replace various older types of metal-enclosed switchgear. It is suitable for 3.6-12kV three-phase, 50Hz AC power grids, serving the purposes of receiving and distributing electrical energy, as well as controlling, monitoring, and protecting circuits. It can be used in single-busbar, single-busbar sectioned, or double-busbar systems.

The switchgear complies with the requirements of standards including IEC 298 “AC Metal-enclosed Switchgear and Controlgear for Rated Voltages Above 1kV and Up to 12kV”, IEC 694 “Common Clauses for High-voltage Switchgear and Controlgear”, China’s GB3906 “AC Metal-enclosed Switchgear for 3.6-40.5kV” and DL404 “Indoor AC High-voltage Switchgear Ordering Conditions”, as well as Germany’s DIN VDE 0670 “AC Switchgear for Rated Voltages Above 1kV”. It also features comprehensive and reliable anti-misoperation functionality.

II. Product Model and Its Designation​

III. Ambient Conditions

◆ Ambient Air Temperature: Upper limit: +40°C, Lower limit: -10°C

◆ Altitude: Not exceeding 1000m

◆ Relative Humidity: Daily average not exceeding 95%, Monthly average not exceeding 90%

◆ Seismic Intensity: Not exceeding magnitude 8

◆ The location shall be free from fire, explosion hazards, severe pollution, chemical corrosion, and severe vibration.

◆ When service conditions exceed the above-mentioned range, the permissible scope and technical measures shall be determined through consultation between the user and our company.

IV. Ordering Instructions

◆ The supply scope of the 10kV withdrawable switchgear is determined based on the configuration wiring diagram provided by the purchaser.

◆ All switchgear are configured with relays, meters, and secondary control equipment according to the secondary wiring drawings provided by the design institute.

◆ The switchgear includes terminal blocks, switches, and disconnectors for external connections. The internal secondary wiring is completed according to the secondary wiring diagram.

V. Technical Parameters

ItemUnitData
Rated voltageKV3,6,7,2,12
Rated frequencyHZ50
Circuit breaker rated currentA630,1250,1600,2000,2500,3150
Switchgear cabinet rated currentA630,1250,1600,2000,2500,3150
Rated dynamic stability current(4S)KA16,20,25,31.5,40,50
Rated stability current(peak value)KA40,50,63,80,100,125
Rated short-circuit breaking currentKA16,20,25,31.5,40,50
Rated short-circuit closing current(peak value)KA40,50,63,80,100,125
Rated insulating level1 min power frequency withstand voltageKA243242
Lightning impulse withstand voltageKA406075
Protection gradeIP2X when shell IP4X, isolation rooms, circuit breaker room door opened