GCS Type Low-voltage Withdrawable Switchgear

I. Product Description

The GCS type Low-voltage Withdrawable Assembled Switchgear (hereinafter referred to as the “Switchgear”) is a product developed by our company to meet the extensive demands of our clientele. It is designed to align with domestic conditions, boasting high technical performance indicators, and is capable of adapting to the evolving needs of the power market while competing with existing imported products. This product is now widely selected by power users. The switchgear is suitable for distribution systems in industries such as power plants, petroleum, chemical, metallurgy, textiles, and high-rise buildings. In locations with high automation levels, such as large-scale power plants and petrochemical systems, which require computer interface compatibility, it serves as a low-voltage assembled distribution device. It is used for power distribution, centralized motor control, and reactive power compensation within three-phase AC systems with a frequency of 50 (60) Hz, a rated operational voltage of 380V (400V, 660V), and a rated current of up to 4000A.

II. Product Model and Its Designation​

III. Ambient Conditions

◆ Ambient Air Temperature: -5°C to +40°C. The daily average temperature does not exceed +35℃. Derating operation may be required based on actual conditions.

◆ Altitude: 2000 meters and below.

◆ Relative Humidity: Does not exceed 50% at the maximum temperature of +40°C. Higher relative humidity is permissible at lower temperatures (e.g., 90% at +20°C). The potential for occasional condensation due to temperature fluctuations should be considered.

◆ The equipment should be installed with a tilt not exceeding 5° from the vertical plane, and the entire switchboard lineup should be relatively level.

◆ The equipment should be installed in a location free from severe vibration and impact, and in an area that will not lead to corrosion of the electrical components and materials.

◆ Users with special requirements may consult with our company’s technical engineers for a solution.

IV. Ordering Instructions

When placing an order, the customer must provide the following information:

◆ The complete product model, including the main and auxiliary circuit diagram numbers.

◆ Single-line diagram of the main circuit system layout/sequence.

◆ Electrical schematic diagram for the auxiliary circuits.

◆ List of components to be installed inside the cabinet.

◆ Setting parameters for the circuits, such as voltage, current, and time.

◆ Any other special requirements that deviate from the product’s normal usage conditions.

V. Technical Parameters

ItemParameter
Rated voltage of main circuit400V、690V
Rated frequency50Hz
Rated insulation voltage690V (1000V)
Rated currentHorizontal busbar below 4000A
Vertical busbar 1000A
Busbar rated short-time withstand current(KA/S)50, 80
Busbar rated peak withstand current(KA/0.1S)105, 176
Rated voltage of auxiliary circuitAC230V、400V、DC110V、220V
Power frequency test voltage (V/5S)2500
1760
Protection gradeIP30, IP40
Busbar setThree-phase four-wire systemA, B, C, PEN
Three-phase five-wire systemA, B, C, PEN, N

Related Products