I. Product Description

GCK (functionally equivalent or superior to GCL) low-voltage withdrawable assembled switchgear (hereinafter referred to as the “Switchgear”) is suitable for rated operational voltages of 380V, in AC three-phase four-wire and three-phase five-wire systems. It is used in power plants, substations, industrial and mining enterprises, and high-rise buildings within power systems for purposes such as power reception, distribution, reactive power compensation, energy metering, lighting, and centralized motor control.

This product complies with the following standards: GB7251 “Low-voltage Switchgear and Controlgear Assemblies”, JB/T9661 “Low-voltage Withdrawable Switchgear”, and IEC 60439-1 “Low-voltage Switchgear and Controlgear Assemblies”.

II. Product Model and Its Designation​

III. Ambient Conditions

◆ Ambient Temperature: -5°C to +40°C, with the average temperature over 24 hours not exceeding +35°C.

◆ Altitude: 2000 meters and below.

◆ Relative Humidity: Shall not exceed 50% at the maximum temperature of +40°C. Higher relative humidity is permissible at lower temperatures (e.g., 90% at +20°C). Potential occasional condensation due to temperature fluctuations should be considered.

◆ The equipment should be installed with a tilt not exceeding 5° from the vertical plane.

◆ The equipment should be installed in a location free from fire, explosion hazards, severe pollution, severe vibration, and impact, and in an area that will not lead to corrosion of the electrical components and materials.

◆ Suitable for transportation and storage within a temperature range of -25°C to +55°C, and can withstand up to +70°C for short periods (not exceeding 24 hours).

◆ Users with special requirements may consult with our company’s technical engineers for a solution.

IV. Ordering Instructions

When placing an order, the customer must provide the following information:

◆ Primary circuit scheme number, equipment model, capacity, and single-line system diagram.

◆ Secondary circuit schematic diagram. If the user does not provide specific requirements, the manufacturer will design according to national standards.

◆ Switchgear lineup arrangement diagram and electrical room floor plan/layout.

◆ Main busbar specification. If not provided by the user, the manufacturer will supply according to standard specifications.

◆ Surface color of the switchgear.

◆ For any other special requirements, the user may consult with our factory.

V. Technical Parameters

ItemParameter
Rated insulation voltage690V、1000V
Rated working voltage400V、690V
Rated voltage of auxiliary circuitAC220V、380V、DC110V、220V
Rated frequency50Hz
Rated currentHorizontal busbar below 4000A
Vertical busbar 630A, 1000A, 1250A
Rated short-time withstand current50、80KA/S Neutral busbar 30KA/S
Rated peak current105KA/0.1S 176KA/0.1S
Functional units (drawer) breaking capacity50KA(effective value)
Shell protection gradeIP30 IP40
Operation modeOn the spot, remote, automatic
Busbar setThree-phase four-wire system, three phase three wire system