220KV Oil-immersed Power Transformer

220KV Oil-immersed Power Transformer

Email: xdhdbyq@gmail.com

Mobile: +8613053855050

Phone: 8618063599126

QQ: 3175898298

Product Details

220KV Oil-immersed Power Transformer

I. Product Description

220kV oil-immersed power transformer is the carefully designed, continuous improved new products, which is combined with existing successful technology and experiences at home and abroad. It has the characteristics of compact and reliable structure, low loss, low noise, excellent performance.

II. Technical Parameters

1. 220KV S11 Series Three-Phase Double-Winding No-Load Voltage Regulation Transformer

Rated Capacity
(KVA)
Voltage Combination and Tapping Range (KV)Connection SymbolNo-Load Loss
(W)
Load Loss
(W)
No-Load Current
(%)
Short-Circuit Impedance
(%)
High-VoltageLow-Voltage
31500220±2×2.5% 242±2×2.5%6.3
6.6
10.5
11
YNd11281280.7012-14
40000331490.70
50000391800.65
63000472090.65
7500010.5
11
13.8
542380.60
90000622740.55
120000753280.55
15000011
13.8 15.75
18 20
903850.50
160000944040.49
1800001024360.46
2400001285390.42
30000015.75
18 20
1516410.38
3600001747350.38
3700001777510.38
4000001877950.35
4200001948250.35

Note:

  • 1. If necessary, rated capacity less than 31500KVA and other voltage combined transformers may be supplied.
  • 2. If necessary, transformer of LV 35KV and 38.5KV may be supplied.
  • 3. Priority to no-tapping structure. If necessary tapping terminals may be set.

2. 220KV SZ11 Series Three-Phase Double-Winding On-Load Tap-Changing Transformers

Rated Capacity
(KVA)
Voltage Combination and Tapping Range (KV)Connection SymolNo-Load Loss
(W)
Load Loss
(W)
No-Load Current
(%)
Short-Circuit Impedance
(%)
High-VoltageMedium-VoltageLow-VoltageUpDown
31500220±2×2.5% 242±2×2.5%69 115 1216.3
6.6
10.5
11
35
37
38.5
YNyn0d11321540.70(H-M):
22-24

(H-L):
12-14

(M-L):
7-9
(H-M):
12-14

(H-L):
22-24

(M-L):
7-9
40000391800.63
50000452140.56
63000532480.56
9000010.5
11
13.8
35
37
38.5
693330.49
120000854100.49
15000011
13.8
15.75
35
37
38.5
1004870.42
1800001145560.42
2400001416840.35
3000001668080.30

Note:

  • 1. Rated Capacity:(100/100/100)% step-up (100/50/100)%;step down (100/50/100)% or (100/50/100)%.
  • 2.If necessary, rated capacity loss than 31500KVA and other voltage combine transformers may be supplied.
  • 3. Priority to no-tapping structure. If necessary tapping terminals may be set.

3. 220KV S11 Series Three-Phase Double-Winding No-Load Voltage Regulation Transformers

Rated Capacity
(kVA)
Voltage Combination and Tapping Range (kV)Connection SymbolNo-Load Loss
(W)
Load Loss
(W)
No-Load Current
(%)
Short-Circuit Impedance
(%)
High-VoltageLow-Voltage
31500220±2×2.5% 242±2×2.5%6.3
6.6
10.5
11
YNd11281280.7012-14
40000331490.70
50000391800.65
63000472090.65
7500010.5
11
13.8
542380.60
90000622740.55
120000753280.55
15000011
13.8
15.75
18
20
903850.50
160000944040.49
1800001024360.46
2400001285390.42
30000015.75
18
20
1516410.38
3600001747350.38
3700001777510.38
4000001877950.35
4200001948250.35

Notes:

  • 1. If necessary, rated capacity less than 31500KVA and other voltage combined transformers may be supplied.
  • 2. If necessary, transformer of LV 35kV and 38.5kV may be supplied.
  • 3. Priority to no-tapping structure. If necessary, tapping terminals may be set.

4. 220KV SZ11 Series Three-Phase Double-Winding On-Load Tap-Changing Transformers

Rated Capacity
(kVA)
Voltage Combination and Tapping Range (kV)Connection SymbolNo-Load Loss (W)Load Loss (W)No-Load Current (%)Short-Circuit Impedance (%)
High-VoltageMedium-VoltageLow-VoltageUpDown
31500220±2×2.5% 242±2×2.5%69 115 1216.3
6.6
10.5
11
35
37
38.5
YNyn0d11321540.70(H-M): 22-24

(H-L): 12-14

(M-L): 7-9
(H-M): 12-14

(H-L): 22-24

(M-L): 7-9
40000391800.63
50000452140.56
63000532480.56
9000010.5
11
13.7
35
37
38.5
693330.49
120000854100.49
15000011
13.8
15.75
35
37
38.5
1004870.42
1800001145560.42
2400001416840.35
3000001668080.30

Notes:

  • 1. Rated capacity for load losses is (100/100/100)%; for step-up structure it is (100/50/100)%; for step-down structure it can be (100/100/50)% or (100/50/100)%.
  • 2. If necessary, rated capacity less than 31500KVA and other voltage combined transformers may be supplied.
  • 3. Priority to no-tapping structure. If necessary, tapping terminals may be set.

5. 220KV SS11 Series Three-Phase Three-Winding No-Load Voltage Regulation Transformers

Rated Capacity
(kVA)
Voltage Combination and Tapping Range (kV)Connection SymbolNo-Load Loss (W)Load Loss (W)No-Load Current (%)Short-Circuit Impedance (%)
High-VoltageLow-Voltage
31500220±8×1.25%6.3
6.6
10.5
11
35
37
38.5
YNd11311280.7012-14
40000361490.63
50000431800.56
63000512090.56
9000010.5
11
35
37
38.5
642740.49
120000793290.49
150000933850.42
1800001084450.42
12000066
69
823370.49
150000963940.42
1800001124510.42

6. 220KV SSZ11 Series Three-Phase Three-Winding On-Load Tap-Changing Transformers

Rated Capacity
(KVA)
Voltage Combination and
Tapping Range (KV)
Connection SymbolNo-Load Loss
(W)
Load Loss
(W)
No-Load Current
(%)
Capacity AllocationShort-Circuit Impedance
(%)
High-VoltageMedium-VoltageLow-Voltage
31500220±8×1.25%69
115
121
6.3
6.6
10.5
11
35
37
38.5
YNyn0d11351540.77100/100/100

100/50/100

100/100/50
(H-M):
12-14

(H-L):
22-24

(M-L):
7-9
40000421800.70
50000482140.63
63000562480.63
9000010.5
11
35
37
38.5
743330.56
120000924100.56
1500001084870.49
1800001255990.49
2400001557410.45

Note:

  • 1. Data listed in the form are used for step-down transformers. Step-up transformers are also available upon request.
  • 2. Rated capacity for load loss:(100/100/100)%.
  • 3. Products with low-voltage of 6.3kV, 6.6kV, 10.5kV, and 11kV are not recommended.

Related Products

Leave A Message