SCBH15-M Series Amorphous Alloy Dry-type Transformer

SCBH15-M Series Amorphous Alloy Dry-type Transformer

Email: xdhdbyq@gmail.com

Mobile: +8613053855050

Phone: 8618063599126

QQ: 3175898298

Product Details

SCBH15-M Series Amorphous Alloy Dry-type Transformer

I. Product Description

Amorphous alloy dry-type transformer is a new kind of low loss dry type transformer model. Due to inherit the traditional dry-type transformer’s advantages of high reliability, flame retardant, and maintenance free, amorphous alloy dry-type transformer has a wide development prospect in market distribution transformer.

SCBH15-M Series Amorphous Alloy Dry-type Transformer

II. Product Features

◆ SCBH15 amorphous alloy dry-type transformer is a new generation of energy-saving transformer.

◆ The material of core adopts amorphous alloy whose no-load loss can be reduced by more than 75% than ordinary S11 using silicon steel sheet as the core.

III. Scope of Application

The transformer is suitable for high-rise buildings, commercial center, subway, airport, station, industrial and mining enterprises or power plants as well as to the highly energy-saving demanding outdoor place.

IV. Technical Parameters

SCBH15-M Series Amorphous Alloy Dry-type Transformer

Rated Capacity (KVA)Voltage combination (KV)Connection SymbolNo-Load Loss(W)Load Loss(W)No-Load Current (%)Short-Circuit Impedance (%)
High-VoltageHigh-Voltage Tapping Range(%)Low-VoltageB 100℃​F 120℃​H 145℃​
1006
6.3
6.6
±5
±2×2.5%
0.4Dyn111301480157016901.24.0
1251501740185019801.1
1601702000213022801.1
2002002370253027101.0
2502502590276029601.0
3153153270347037300.9
4004003750399042800.8
5005004590488052300.8
6306305610596064000.76.0
8008006550696074600.7
100010007650813087600.6
1250125091009690103700.6
160016001105011730125800.6
200020001360014450155600.5
250025001615017170184500.5
160016001228012960139000.68.0
200020001502015960171100.5
250025001776018890202900.5

Note:

  1. Load losses listed in the table are the values under reference temperature (see GB1094.11 provisions) corresponding to insulation heat resistant levels within brackets.
  2. Specific requirements should be consulted between the manufacturer and the customer when other connection group are taken.

Related Products