Amorphous alloy dry-type transformer is a new kind of low loss dry type transformer model. Due to inherit the traditional dry-type transformer’s advantages of high reliability, flame retardant, and maintenance free, amorphous alloy dry-type transformer has a wide development prospect in market distribution transformer.

◆ SCBH15 amorphous alloy dry-type transformer is a new generation of energy-saving transformer.
◆ The material of core adopts amorphous alloy whose no-load loss can be reduced by more than 75% than ordinary S11 using silicon steel sheet as the core.
The transformer is suitable for high-rise buildings, commercial center, subway, airport, station, industrial and mining enterprises or power plants as well as to the highly energy-saving demanding outdoor place.
| Rated Capacity (KVA) | Voltage combination (KV) | Connection Symbol | No-Load Loss(W) | Load Loss(W) | No-Load Current (%) | Short-Circuit Impedance (%) | ||||
| High-Voltage | High-Voltage Tapping Range(%) | Low-Voltage | B 100℃ | F 120℃ | H 145℃ | |||||
| 100 | 6 6.3 6.6 | ±5 ±2×2.5% | 0.4 | Dyn11 | 130 | 1480 | 1570 | 1690 | 1.2 | 4.0 |
| 125 | 150 | 1740 | 1850 | 1980 | 1.1 | |||||
| 160 | 170 | 2000 | 2130 | 2280 | 1.1 | |||||
| 200 | 200 | 2370 | 2530 | 2710 | 1.0 | |||||
| 250 | 250 | 2590 | 2760 | 2960 | 1.0 | |||||
| 315 | 315 | 3270 | 3470 | 3730 | 0.9 | |||||
| 400 | 400 | 3750 | 3990 | 4280 | 0.8 | |||||
| 500 | 500 | 4590 | 4880 | 5230 | 0.8 | |||||
| 630 | 630 | 5610 | 5960 | 6400 | 0.7 | 6.0 | ||||
| 800 | 800 | 6550 | 6960 | 7460 | 0.7 | |||||
| 1000 | 1000 | 7650 | 8130 | 8760 | 0.6 | |||||
| 1250 | 1250 | 9100 | 9690 | 10370 | 0.6 | |||||
| 1600 | 1600 | 11050 | 11730 | 12580 | 0.6 | |||||
| 2000 | 2000 | 13600 | 14450 | 15560 | 0.5 | |||||
| 2500 | 2500 | 16150 | 17170 | 18450 | 0.5 | |||||
| 1600 | 1600 | 12280 | 12960 | 13900 | 0.6 | 8.0 | ||||
| 2000 | 2000 | 15020 | 15960 | 17110 | 0.5 | |||||
| 2500 | 2500 | 17760 | 18890 | 20290 | 0.5 | |||||
Note: